PowerLogic Split Core Current Transformer – Type HJ, for cable – 0750A / 5A


Main

range PowerLogic
product name CT
product or component type Current transformer
secondary current 5 A
accuracy class Class 0.5 at 2.5 VA
[In] rated current 750 A

Complementary

current transformer type Standard for cable
Split core
current transformer ratio 750/5
[Ith] conventional free air thermal current 900 A
maximum safety factor 5
permissible current 45000 A during 1 s
[Ue] rated operational voltage < 720 V 50 Hz
[Ui] rated insulation voltage 3 kV
mounting mode Clip-on
width 67 mm outside:
height 96 mm outside:
diameter 42.4 mm inner:
electrical insulation class Class E
cable outer diameter 42.4 mm
connections – terminals Cable 2 cable(s) 0.5…1.5 mm² 0.5 m

Environment

standards DIN EN 60044-1
DIN EN 61869-1
DIN EN 61869-2
VDE 0414
ambient air temperature for operation -5…50 °C
ambient air temperature for storage -25…70 °C

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 474.0 g
Package 1 Height 8.5 cm
Package 1 width 7 cm
Package 1 Length 10 cm
Unit Type of Package 2 S02
Number of Units in Package 2 16
Package 2 Weight 8.06 kg
Package 2 Height 15 cm
Package 2 width 30 cm
Package 2 Length 40 cm