LV CT 1000 A – 0.333 V output – split core CT – 62 mm x 201 mm


Main

range PowerLogic
device short name LVCT
product or component type Current transformer
output voltage 0.333 V
electrical connection Cable: 1.8 m (AWG 18) 600 V
product destination BCPM
BCPMSC
Enercept
IEM3000
EM3500
EM4200
EM4900
accessory / separate part category Measurement accessory
current transformer type Split core balance
[In] rated current 1000 A
network frequency 50/60 Hz

Complementary

range compatibility PowerLogic BCPM BCPMA multi-circuit energy meter
PowerLogic BCPM BCPMB multi-circuit energy meter
PowerLogic BCPM BCPME multi-circuit energy meter
PowerLogic BCPMSC BCPMSCA multi-circuit energy meter
PowerLogic BCPMSC BCPMSCB multi-circuit energy meter
PowerLogic BCPMSC BCPMSCE multi-circuit energy meter
PowerLogic EM3500 EM3502 energy meter
PowerLogic EM3500 EM3550 energy meter
PowerLogic EM3500 EM3555 energy meter
PowerLogic EM3500 EM3560 energy meter
PowerLogic EM3500 EM3561 energy meter
PowerLogic EM4200 EM4235 energy meter
PowerLogic EM4200 EM4236 energy meter
PowerLogic EM4900 EM4904 multi-circuit energy meter
PowerLogic EM4900 EM4908 multi-circuit energy meter
PowerLogic EM4900 EM4914 multi-circuit energy meter
PowerLogic EM4900 EM4928 multi-circuit energy meter
Acti 9 iEM3000 iEM3455 energy meter
Acti 9 iEM3000 iEM3465 energy meter
measurement accuracy 1 % 10…100 %

Environment

relative humidity 95 %
ambient air temperature for operation -15…60 °C
ambient air temperature for storage -40…70 °C
width 62 mm internal:
151 mm external:
depth 30 mm
height 139 mm internal:
201 mm external:
net weight 0.87 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 1.224 kg
Package 1 Height 10.2 cm
Package 1 width 21 cm
Package 1 Length 25.4 cm

Contractual warranty

Warranty 18 months