BCPM power monitoring advanced ethernet – 42 solid core 100A – 18mm CT spacing


Main

range PowerLogic
product name PowerLogic BCPM
product or component type Multi-circuit energy meter
device short name BCPME
Model type Advanced + ethernet
power monitoring Basic instrumentation
energy management Sub billing and cost allocation
device application Sub billing
power quality analysis voltage sag and swell detection
type of measurement Voltage
Current
Frequency
Active power
Power factor
Active energy
[Us] rated supply voltage 90…277 V AC 50/60 Hz +/- 1 %
network frequency 50 Hz
60 Hz

Complementary

current transformer input Solid core CT 100 A42 x
update time 1.8 s
measurement voltage 90…277 V phase to neutral
150…480 V phase to phase
measurement accuracy Branch current 2 % 0.25…2 A
Branch current 1 % 2…100 A
Mains current 3 % 1…100 %
Mains current 3 % 2…100 %
Voltage 1 % 90…277 V
sampling rate 256 samples/cycle
connection pitch 18 mm
provided equipment 42 x current transformer
2 x cables
communication port protocol Modbus RTU
BACnet IP
BACnet MS/TP
Modbus TCP
SNMP v2
communication port support RS485
Ethernet
communication of data High-high current alarm
Under voltage alarm
Over voltage alarm
Low-low current alarm
High current alarm
Low current alarm

Environment

mounting mode Panel-mounted
mounting support Panel
Enclosure
relative humidity 0…95 % at 0…60 °C
ambient air temperature for storage -40…70 °C
operating altitude 3000 m
standards IEC 61036
UL 508
ANSI C12.1
EN 61010
product certifications UL
width 253 mm
depth 71 mm
height 307 mm
net weight 1.5 kg

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 7.008 kg
Package 1 Height 33.1 cm
Package 1 width 33.1 cm